Accuracy ± (0.3% of reading + 1digit)
Single loop temperature controllers
48mm x 48mm size CB100
48mm x 96mm size CB400
96mm x 48mm size CB500
72mm x 72mm size CB700
96mm x 96mm size CB900

CB100 temperature controller

Temperature controller CB100


A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 48 x 48 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Dustproof and waterproof protection : IP66
Go to "Quick Reference Guide" Index Page.
Go to Page Top

CB400 temperature controller




A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 48 x 96 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Heater break alarm, Loop break alarm)
Dustproof and waterproof protection : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top

CB500 temperature controller

CB500


A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 96 x 46 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Heater break alarm, Loop break alarm)
Dustproof and waterproof protection : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top

CB700 temperature controller

Temperature controller CB700


A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 72 x 72 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Heater break alarm, Loop break alarm)
Dustproof and waterproof protection : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top

CB900 temperature controller

CB900


A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control ( with autotuning and self-tuning function )
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 96 x 96 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Heater break alarm, Loop break alarm)
Dustproof and waterproof protection : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top
Back RKC INSTRUMENT INC.