48mm x 48mm size
Products Typical functions
CB100 Standard temperature controller Communication, Large-size LED display
CB103 Standard temperature controller Analog retransmission output
SA100 Socket installation type temperature controller Socket installation
REX-D100 Standard temperature controller Universal input, Advanced fuzzy logic
REX-P24 Lamp/Soak temperature controller Program (two patterns), Timer control

CB100 Temperature Controller

Temperature controller CB100


A catalog download is here.

CB_05E.pdf (227KB)
(CB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications RS-485
External Dimensions 48 x 48 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Dustproof and waterproof protection : IP66
Go to "Quick Reference Guide" Index Page.
Go to Page Top

CB103 Temperature Controller

Temperature controller CB103


A catalog download is here.

CB3_03E.pdf (191KB)
(CB3 series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Triac trigger output
Triac output
Communications None
External Dimensions 48 x 48 x 100mm (W x H x D)
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Auxiliary output ( Alarm or RUN/STOP staus, Analog output )
Contact input : 1 point
Dustproof and waterproof protection : IP66
Go to "Quick Reference Guide" Index Page.
Go to Page Top

SA100 Temperature Controller
Temperature controller SA100


A catalog download is here.

SA100_01E.pdf (418KB)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy Thermocouple
±(1% of reading + 1 digit) or ±2°C (4°F) whichever is larger

RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger

DC voltage and DC current
±(0.3% of span + 1 digit)
Out of an accuracy guarantee range Thermocouple R, S, B : 0 to 399°C
Thermocouple T, U : Less than -100°C
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output : 4 to 20mA
Communications RS-485
External Dimensions 48 x 48 x 70mm (W x H x D)
* Socket does not include it.
Standard function RUN/STOP switching
Optional function Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Contact input : 2 points
Dustproof and waterproof protection : IP66
Go to "Quick Reference Guide" Index Page.
Go to Top Page

REX-D100 Temperature Controller

Temperature controlle REX-D100


A catalog download is here.

D_01E.pdf (79.6KB)
(D series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Universal input
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals.
Sampling time 0.5 sec.
Measuring accuracy ±(0.3% of spsn + 1 digit)
Cold junction temperature compensation error Within ±1.5°C (between 0 and 50°C)
Control method PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.

Heat/cool PID control (with autotuning and self-tuning function)
Control output type Relay contact output
Voltage pulse output
DC current output
DC voltage output
Communications RS-485
External Dimensions 48 x 48 x 100mm (W x H x D)
Standard function Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Optional function Heater break alarm (Single-phase, Three-phase)
Contact input
Analog output
Dustproof and waterproof protection : NEMA4X
Go to "Quick Reference Guide" Index Page.
Go to Page Top

REX-P24 Ramp/Sork Temperature Controller
Ramp / Sork temperature controller REX-P24


A catalog download is here.

P24_01E.pdf(61.4KB)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Storage program pattern Max. 2 patterns (8 segments per pattern)
Input Thermocouple, RTD
Sampling time 0.5 sec.
Measuring accuracy ±(0.3% of spsn + 1 digit)
Cold junction temperature compensation error Within ±1.5°C (between 0 and 50°C)
Control method PID control (with autotuning function)
* ON/OFF, P, PI and PD control are also selectable.
Control output type Relay contact output
Voltage pulse output
DC current output
Communications None
External Dimensions 48 x 48 x 100mm (W x H x D)
Standard function Timer control
Optional function Level PID (4 level)
Contact output : Up to 2 points (Temperature alarm, Pattern end, Time signal, Time-up)
Contact input : 2 points (STOP/START, RESET/RUN, RESET/START)
Dustproof and waterproof protection : NEMA4X
Go to "Quick Reference Guide" Index Page.
Go to Page Top

Back RKC INSTRUMENT INC.