| D Series Specifications |
| Input | |||||||||||
| Input (Universal input) |
|
||||||||||
| Input Range | See Range and Input Code Table | ||||||||||
| Sampling Time | 0.5 sec | ||||||||||
| PV Bias | Temperature input : -1999(-199.9) to 9999(999.9)°C[°F] DC voltage, DC current : -1999 to 9999 (A decimal point position is the same as that of PV.) |
||||||||||
| Range and Input Code Table (Field-programmable) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 1: Type B input : Accuracy is not guaranteed between 0 and 400°C (0 and 752°F). 2: Type N, PLII and W5Re/W26Re input : Accuracy is not guaranteed between 0 and 32°F. 3: DC current input : A 250W resistor is externally connected at the input terminals. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Performance | |||||||||
| Measuring Accuracy |
|
||||||||
| Insulation Resistance | More than 20MW (500V DC) between measured terminals and ground. More than 20MW (500V DC) between power terminals and ground. |
||||||||
| Dielectric Strength | 1000V AC for one minute between measured terminals and ground. 1500V AC for one minute between power terminals and ground. |
||||||||
| Control | |||||||||||||||||||||||||
| Control Method |
|
||||||||||||||||||||||||
| Major Setting Range |
|
||||||||||||||||||||||||
| Control Output |
|
||||||||||||||||||||||||
| Combination of Output and Type | |||
| Output \ Type | D100 Specify when ordering |
D400/D900 (OUT1) Universal output |
D400/D900 (OUT2) Specify when ordering |
| Relay contact | Available | Available | Available |
| Voltage pulse | Available | Available | Available |
| Current | Available | Available | Available |
| Continuous voltage | Available | Not available | Available |
| Alarms | |||||||||
| Temperature Alarm |
|
||||||||
| Control Loop Break Alarm (LBA) |
OR output with temperature alarm is available. Not available for heat/cool type. |
||||||||
| Heater Break Alarm (Optionl) |
OR output with temperature alarm is available. |
||||||||
| Alarm Output | Relay output, Form A contact 250V AC 0.5A (resistive load) | ||||||||
| External Contact Input | |
| Number of inputs | 1 point |
| Type | SV1/SV2 selection (Open : SV1, Close : SV2) |
| REX-D400/900: Standard function, REX-D100: Optional function | |
| Analog Output (Optional) | |
| Number of outputs | 1 point |
| Output signal | 0 to 5V, 0 to 10V, 1 to 5V DC (Load resistance : More than 1kW) 0 to 20mA, 4 to 20mA DC (Load resistance : Less than 600W) |
| Output data can be selected among process value, deviation, set point, manipulated output value (Heat-side or Cool-side), current transformer input (With HBA function). | |
| Communications (Optional) | |||||||||
| Communication Method | RS-485 (2-wire), RS-422A(4-wire) | ||||||||
| Communication Speed | 1200, 2400, 4800, 9600, 19200 BPS | ||||||||
| Bit Format |
|
||||||||
| Communication Code | ASCII (JIS) 7-bit code | ||||||||
| Maximum Connection | 31 (Address can be set from 0 to 99.) | ||||||||
| Waterproof/Dustproof (Optional) | |||
| CB100 : | IP66 | ||
| CB400/500/700/900 : | IP65 | ||
|
|||
| General Specifications | |||||||
| Supply Voltage |
|
||||||
| Power Consumption |
|
||||||
| Power Failure Effect | A power failure of 20 msec or less will not affect the control action. | ||||||
| Operating Environments | 0 to 50°C [32 to 122°F] , 45 to 85% RH | ||||||
| Memory Backup | Backed up by EEPROM. Number of writing : Approx. 100,000 times |
||||||
| Net Weight |
|
||||||
| External Dimensions (W x H x D) |
|
||||||
| Compliance with Standards | |
| CE Mark UL Recognized CSA Certified |