Accuracy ± (0.1% of reading + 1digit)
Process / Temperature Controller
48mm x 96mm size FB400
HA400 (Two channels in One controller)
96mm x 96mm size FB900
HA900 (Two channels in One controller)

FB400 Process / Temperature Controller

FB400 temperature controller product photo


A catalog download is here.

FB_03E.pdf (1.01MB)
(FB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
Sampling time 0.1 sec.
0.05 sec. / 0.25 sec. is selectable.
Measuring accuracy Thermocouple : K, J, T, E, PLII
Less than -100°C : ±1.0°C
-100 to 500°C : ±0.5°C
More than 500°C : ±(0.1% of reading + 1 digit)

Thermocouple : N, S, R, W5Re/W26Re
Less than -100°C : ±2.0°C
-100 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

Thermocouple : B
Less than 400°C : ±70.0°C
400 to 1000°C : ±(1.4°C + 1 digit)
More than 1000°C : ±(0.1% of reading + 1 digit)

RTD
Less than 200°C : ±0.2°C
More than 200°C : ±(0.1% of reading + 1 digit)

DC voltage and DC current
±(0.1% of span)
Cold junction temperature compensation error ±1.0°C (between 5 to 40°C)
With in ±1.5°C
(between -10 to +5°C , between 40 to 50°C)
Control method Brilliant II PID control
(with autotuning and startup tuning)
Brilliant II PID control Heat/Cool type
(with autotuning)
Position proportioning control l without feedback resistance (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output
DC voltage output
SSR (Triac) output
Open collector output (Sink type)
Communications Communication 1
RS-232C
RS-422A
RS-485
* MODBUS

Communication 2 (Inter-controller communication)
RS-485
External Dimensions 48 x 96 x 60mm (W x H x D)
Standard function Memory area : 8 areas
Digital input : 3 points (Mode selection)
Remote setpoint input
Waterproof/Dustproof : NEMA4X, IP66
(Waterproof/Dustproof protection only effective from the front in panel mounted installation.)
Optional function Ivent (alarm) output : Max. 4 points
Digital input : 4 points (Memory area selection + Area set)
Heater break alarm
Analog retransmission output : 1 point
Position resistance input
Power feed forward function
Go to "Quick Reference Guide" Index Page.
Go to Page Top

HA400 Process / Temperature Controller




A catalog download is here.

HA_01E.pdf(533KB)
(HA series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* Number of inputs : 2 points
Sampling time 0.025 sec.
Measuring accuracy Thermocouple : K, J, T, E, PLII
Less than -100°C : ±1.0°C
-100 to 500°C : ±0.5°C
More than 500°C : ±(0.1% of reading + 1 digit)

Thermocouple : N, S, R, W5Re/W26Re
Less than -100°C : ±2.0°C
-100 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

Thermocouple : B
Less than 400°C : ±70.0°C
400 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

RTD
Less than 200°C : ±0.2°C
More than 200°C : ±(0.1% of reading + 1 digit)

DC voltage and DC current
±(0.1% of span)
Cold junction temperature compensation error ±1.0°C (at 23°C ± 2°C)
±1.5°C (between 0 to 50°C)
Control method Brilliant PID control (with enhanced autotuning)
Position proportioning control
Control output type Relay contact output
Voltage pulse output
DC current output
DC voltage output
Communications Number of communications : 2 points
RS-232C
RS-422A
RS-485
* MODBUS, DeviceNet, Profibus supported.
External Dimensions 48 x 96 x 100mm (W x H x D)
Standard function Memory area : 16 areas
Cascade control (only 2 channel type)
Optional function Ivent (alarm) output : Max. 4 points
Ivent input : 7 points
Remote set value function
Heater break alarm
Analog retransmission output : 3 points
Position feedback resistance input
(Position proportioning control)
Power feed forward function
Waterproof/Dustproof : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top

FB900 Process / Temperature Controller

FB900 temperature controller product photo


A catalog download is here.

FB_03E.pdf (1.01MB)
(FB series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
Sampling time 0.1 sec.
0.05 sec. / 0.25 sec. is selectable.
Measuring accuracy Thermocouple : K, J, T, E, PLII
Less than -100°C : ±1.0°C
-100 to 500°C : ±0.5°C
More than 500°C : ±(0.1% of reading + 1 digit)

Thermocouple : N, S, R, W5Re/W26Re
Less than -100°C : ±2.0°C
-100 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

Thermocouple : B
Less than 400°C : ±70.0°C
400 to 1000°C : ±(1.4°C + 1 digit)
More than 1000°C : ±(0.1% of reading + 1 digit)

RTD
Less than 200°C : ±0.2°C
More than 200°C : ±(0.1% of reading + 1 digit)

DC voltage and DC current
±(0.1% of span)
Cold junction temperature compensation error ±1.0°C (between 5 to 40°C)
With in ±1.5°C
(between -10 to +5°C , between 40 to 50°C)
Control method Brilliant II PID control
(with autotuning and startup tuning)
Brilliant II PID control Heat/Cool type
(with autotuning)
Position proportioning control l without feedback resistance (with autotuning)
Control output type Relay contact output
Voltage pulse output
DC current output
DC voltage output
SSR (Triac) output
Open collector output (Sink type)
Communications Communication 1
RS-232C
RS-422A
RS-485
* MODBUS

Communication 2 (Inter-controller communication)
RS-485
External Dimensions 96 x 96 x 60mm (W x H x D)
Standard function Memory area : 8 areas
Digital input : 3 points (Mode selection)
Remote setpoint input
Waterproof/Dustproof : NEMA4X, IP66
(Waterproof/Dustproof protection only effective from the front in panel mounted installation.)
Optional function Ivent (alarm) output : Max. 4 points
Digital input : 4 points (Memory area selection + Area set)
Heater break alarm
Analog retransmission output : 1 point
Position resistance input
Power feed forward function
Go to "Quick Reference Guide" Index Page.
Go to Page Top

HA900 Process / Temperature Controller

HA900


A catalog download is here.

HA_01E.pdf(533KB)
(HA series)


Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required.
Input Thermocouple, RTD, DC voltage, DC current
* Number of inputs : 2 points
Sampling time 0.25 sec.
Measuring accuracy Thermocouple : K, J, T, E, PLII
Less than -100°C : ±1.0°C
-100 to 500°C : ±0.5°C
More than 500°C : ±(0.1% of reading + 1 digit)

Thermocouple : N, S, R, W5Re/W26Re
Less than -100°C : ±2.0°C
-100 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

Thermocouple : B
Less than 400°C : ±70.0°C
400 to 1000°C : ±1.0°C
More than 1000°C : ±(0.1% of reading + 1 digit)

RTD
Less than 200°C : ±0.2°C
More than 200°C : ±(0.1% of reading + 1 digit)

DC voltage and DC current
±(0.1% of span)
Cold junction temperature compensation error ±1.0°C ( at 23°C ± 2°C )
±1.5°C ( between 0 to 50°C )
Control method Brilliant PID control (with enhanced autotuning)
Position proportioning control
Control output type Relay contact output
Voltage pulse output
DC current output
DC voltage output
Communications Number of communications : 2 points
RS-232C
RS-422A
RS-485
* MODBUS, DeviceNet, Profibus supported.
External Dimensions 96 x 96 x 100mm ( W x H x D )
Standard function Memory area : 16 areas
Cascade control ( only 2 channel type )
Optional function Ivent (alarm) output : Max. 4 points
Ivent input : 7 points
Remote set value function
Heater break alarm
Analog retransmission output : 3 points
Position feedback resistance input
(Position proportioning control)
Power feed forward function
Waterproof/Dustproof : IP65
Go to "Quick Reference Guide" Index Page.
Go to Page Top

Back RKC INSTRUMENT INC.