Products

Power Controllers

Three phase power controller
THW-A

  • Maximum load capacity: 20A, 30A, 45A, 60A, 80A, 100A
  • Supply voltage: 100 to 240V ac, 400 to 440V ac
  • Control method: Phase control, Zero-cross control
  • Constant current control, Constant voltage control, constant power control
  • Easy setup using keypad and front display
  • Temperature
Download
  • Main features
  • Main specification
  • External dimensions
  • Models

Main features

Digital control provides excellent response and reproducibility

Digital control power controller with a front display and a keypad.

Setting zero for Soft-Start/Soft-Down provides quick response suitable for rapid thermal processes.

Capable of controlling heaters with special characteristics

Since the following control modes (Constant voltage control, Constant current control, Constant power control) are available, this power controller can control heaters in which resistance value greatly changes according to temperature change. Such heaters include Superkanthal and SiC heaters.

Abundant functions are available as standard

Standard functions include External contact input, Soft-Start/Soft-Down, Manual/Auto switch-over, Gradient setting, Output limiter, Output bias, Input-Phase angle proportional/Input-Voltage proportional/Input-Power phase angle switch-over.

Main specification

  • Control method: Phase control/Zero-cross control (switchable)
  • Maximum load capacity: 20A, 30A, 45A, 60A, 80A, 100A
  • Applicable load: Linear load (R:Resistance) (when in phase control: Primary side control of transformer is available. Magnetic flux density must be 8000 Gauss or less)
  • Input signal:

1) Group 1 (configurable within the group)

4 to 20mA, 0 to 20mA, 0 to 5V, 1 to 5V, 0/12V dc, Dry contact input

2) Group 2 (configurable within the group)

0 to 10V, 0/12V, 0/24V dc, Dry contact input

  • Output mode:
    Constant voltage control, Phase angle proportional, Voltage proportional, Proportional square voltage, Square voltage feedback, Constant current control (optional), Constant power control (optional)
  • Power supply frequency: 50/60Hz (automatically selected)
  • Standard functions:
    Auto/Manual switch-over (External manual setting is optional),
    Gradient setting function (External setting is optional),
    Soft-Start/Soft-down function, External contact input (DI) 3 points,
    Dry contact input (RUN/STOP, Auto/Manual switch-over, Alarm interlock release,
    Heater break alarm enable/disable, Soft-Start enable/disable, Key lock enable/disable, Overcurrent alarm enable/disable, Memory area switching
    *Heater break alarm and Overcurrent alarm are optional
    On/Off control (external high limit and low limit setting are optional)
    Alarm output: 2 points

<Optional functions>

  • Heater break alarm (Memory area: 4 points), Current limiter

<General specification>

  • Ambient temperature: Range of guaranteed performance 0 to 40°C, Operation guarantee range -15 to +55°C
  • Power supply voltage (Rating): 200 to 240V AC, 400 to 440V ac
    *Control circuit: Rating 200 to 240V ac
  • Weight:
    200V 20 to 60A type Approx. 5.8kg,
    400V 20 to 60A type Approx.10.3kg,
    200V and 400V 80A/100A types: Approx.13.6kg

External dimensions

Models